BLDGTYP / design-phase report
Yun Architecture SOHO Townhouse
Envelope

Below we have included recommendations for the building envelope assemblies based on the Energy model results shown in previous sections. These are recommendations only and should be reviewed by the design team to ensure they are appropriate for the project.

The following assembly U-values have been assessed using project-specific energy-model inputs and supporting thermal-bridge assumptions. Assembly diagrams should be treated as performance targets and coordination references, not final construction documents.

SmartRock Reference:

Structural coordination All structural member sizing and spacing must be provided by the Structural Engineer and/or Architect. Sizing and spacing shown here is related to target insulation levels only.

Ext. Wall - Front

Ext. Wall - Front assembly diagram
  • Primary airtightness layer to be Pro-Clima Visconn or sim. liquid applied airseal applied to inside of face of existing masonry.
  • 3-1/2” SmartRock mineral-fiber + Intello installed inside of existing masonry wall.
  • 2x service cavity stud wall installed inside of SmartRock insulation layer.
  • Use ‘Service Cavity’ on interior side for all plumbing and electrical. Reduce penetrations through the air-barrier to improve building airtightness.

Ext. Wall - Rear

Ext. Wall - Rear assembly diagram
  • Primary airtightness layer to be Pro-Clima Visconn or sim. liquid applied airseal applied to inside of face of new CMU wall.
  • 3-1/2” SmartRock mineral-fiber + Intello installed inside of new CMU masonry wall.
  • 2x service cavity stud wall installed inside of SmartRock insulation layer.
  • Use ‘Service Cavity’ on interior side for all plumbing and electrical. Reduce penetrations through the air-barrier to improve building airtightness.

Floor

Floor assembly diagram
  • Note: All concrete sizing as per Structural Engineer. Concrete is shown for illustration purposes only.
  • Target. 6” sub-slab (Neopor Graphite EPS or sim.).
  • Install foam insulation in 2 layers of 2”, offset all board edges min 12”, fill all voids with low-expansion spray foam.
  • Sub-slab air and vapor barrier to be installed directly below concrete (above insulation). Use 15 Mil StegoHome or similar
  • Tape / Seal all penetrations and seams of sub-slab air and vapor barrier with StegoTape / StegoMastic or similar.

Roof - Deck

Roof - Deck assembly diagram
  • Install continuous insulation over wood-framed floor structure. Use min. 4” XPS foam insulation or sim.
  • Use adhered insulation where possible (avoid metal fasteners)
  • Primary air-barrier to be Intello Plus air and moisture vapor-retarder installed along underside of all roof joists. If preferred, substitute A/C plywood. Tape all seams to ensure air and moisture-vapor tight.
  • Use service cavity / drop-ceiling below air/vapor retarder membrane for all plumbing, electrical, and / or lighting fixtures.
  • Note: when constructing un-vented insulated rafter assemblies follow all code requirements as per Residential Code of NYS 2025 section 806.5
  • If constructing the roof without venting, min R-20 insulation should be used above/outside the primary sheathing layer. R-20 can be achieved by:
  • 5” EPS foam board
  • 4” of GPS foam board
  • 4” of XPS foam board
  • 4” of Polyisocyanurate foam board.

Roof - Sloped

Roof - Sloped assembly diagram
  • Install mineral fiber batt insulation with sheathing-vent.
  • Note: when constructing vented rafter assemblies follow all roof ventilation code requirements as per Residential Code of NYS 2025 section 806.1
  • Primary air-barrier to be Intello Plus air and moisture vapor-retarder installed along underside of all roof joists. If preferred, substitute A/C plywood. Tape all seams to ensure air and moisture-vapor tight.
  • Use service cavity / drop-ceiling below air/vapor retarder membrane for all plumbing, electrical, and / or lighting fixtures.
  • In order to achieve sufficient assembly R-Value, insulate service cavity with mineral fiber batt insulation.

02

Building Airtightness

The primary role of airtightness in buildings is to avoid interstitial condensation and mold/moisture damage to the structure during the winter and shoulder-season months. Additionally, in hot climates, airtightness plays an important role in restricting warm outdoor air and moisture vapor ingress from the exterior. This helps reduce energy consumption needed for cooling and dehumidification while improving occupant comfort and building resiliency.

As well as its role in ensuring building durability, airtightness levels have a simple linear relationship to the building’s heat loss: the more airtight the construction, the less heat is lost in winter and the better the energy performance. In addition, airtightness has a large effect on indoor relative humidity during the summer months with a corresponding reduction of cooling energy consumption and dehumidification need.

Code-minimum construction in most states requires an airtightness rate of somewhere between 3 to 7 air-changes per hour (ACH), and the NYC Energy Code 2025 / Zone 4(A) requires residential buildings in Climate Zones 3 to 8 to demonstrate an airtightness level of less than 3.0 ACH@50Pa.

In order to meet the recommended building performance level, this project should target an airtightness level of better than 1.0 ACH@50Pa. Improving airtightness to this low level is one of the best ways to improve performance, increase comfort and durability, and reduce the risk of uncontrolled wintertime air leakage.

Winter Heat Loss due to Envelope Air Leakage

EnerPHit by Component shown across a range of blower-door results.

Winter Heat Loss due to Envelope Air Leakage Chart showing annual winter heat loss from envelope air leakage as airtightness increases from 0 to 10 ACH at 50 Pascals. Typical Construction1 ACH: 1,167 kWh/a3 ACH: 3,500 kWh/aTarget: 1 ACH@50NYC Energy Code 2025 / Zone 4(A): 3 ACH@5002,0004,0006,0008,00010,00012,00014,000012345678910 Air-Changes / Hour (ACH) @ 50 Pascals Building Heat Loss (kWh/yr)

03

Masonry Rowhouse Air-Sealing Primer

BLDGTYP has prepared a comprehensive Masonry Rowhouse Air-Sealing Primer for masonry townhouse projects. The primer covers the value of air-sealing, common air-sealing methods for typical NYC masonry residential assemblies, recommended products, and testing strategies.

Download the Masonry Rowhouse Air-Sealing Primer [12 MB]

Preview collage of the Masonry Rowhouse Air-Sealing Primer cover and interior pages.

04

AeroBarrier

AeroBarrier spray nozzle applying aerosolized sealant inside a framed building.

Achieving Passive House levels of airtightness in existing buildings can be challenging. The dedicated air barrier layers described above will provide excellent, durable airtightness. The goal should be to achieve Passive House airtightness levels with the dedicated air barrier systems described above. However, some areas may be inaccessible due to existing conditions or otherwise impractical to expose in order to accomplish perfect air sealing. In cases where air sealing results are uncertain, we recommend having a backup plan in place.

AeroBarrier provides whole-building air sealing using an aerosolized polymer that “finds” leaks and seals them. We recommend consulting early in the build with an AeroBarrier installer so that they can be included in the project schedule should their services be required.